AT-102-3000MR/MRS – Photohelic® Explosion-proof ATEX/IECEx Exd pressure gauge/pressure switch


• Switch type: each setpoint has 1 type C relay (SPDT). Setpoint adjustment via front knobs.
• Repeatability ±2%
Product details
Atex:
II 2G Ex db IIC T5,T6 Gb -60°C≤Ta≤+50°C (T6)
-60°C≤Ta≤+60°C (T5)
II 2D Ex tb IIIC T75°C Db,
IECEx:
Ex db IIC T5, T6 Gb -60°C ≤Ta ≤+50°C (T6)
-60°C ≤Ta ≤+60°C (T5)
Ex tb IIIC T75°C Db
Execution:
IP66 (IP65 versions VS1-VS2-VL1)
- Suitable for: clean, dry air and compatible gases.
- Wet parts: ask the manufacturer.
- Temperature limits:
• Magnesense®: from -18 to 66°C.
• Enclosure:-76 to 140°F (-60 to 60°C)* T5
(-60 to 50°C) T6 - Pressure limits: see technical data sheet
- Precision:
• ±1% fs for ranges: 0.25”, 0.5”, 2”, 5”, 10”, 15”, 25”, 50 Pa, 100 Pa, 500 Pa, 1250 Pa, 2 KPa, 3 KPa, 5 KPa.
• 2% for the fields: 0.1”-1”, 25 Pa, 250 Pa and all bidirectional fields. - Stability: ±1% fs / year.
- Power supply:
10 … 35 Vdc (2-wire);
17 … 36 Vdc or isolated;
21.6 … 33 Vac (3-wire). - Output signals: 4-20 mA (2-wire); 0-5 VDC, 0-10 VDC (3-wire).
- Response time: up to 80 sec with “STD” pressure taps and 40 sec with “LD” pressure taps mainly on low ranges. “LD” option recommended up to 125 Pa (VL0-VL1).
- Mounting: with diaphragm in vertical position.
- Case Material: aluminum (stainless steel option).
- Refuse: epoxy RAL7015 (case) and RAL 5015 (lid) (only for aluminium version).
- Pressure gauges: threaded 1/8” NPT F brass (optional stainless steel). In the presence of acetylene, stainless steel is required.
- Electrical inputs: 2 x 1/2” NPT F standard (cable gland not included).
- Dimensions: see drawing
- Weight: 5 kg approx. (blind).
SPECIFICATIONS Switch Type :Each setpoint has 1 type C relay (SPDT).
Relay contacts: (resistive) 1 Form C rated 1,0 A @ 30Vdc, 0,3A @ 110 Vdc or 0,5A @ 125 Vac.
Electrical connections: 46 cm cable with 8 conductors
Diet : 24 Vdc ±10%.
Installation position: diaphragm in vertical position
Set point adjustment: front knobs.
CAUTION USE ONLY WITH AIR OR COMPATIBLE GAS!
CONTACT THE FACTORY FOR USE WITH GAS OTHER THAN AIR OR NITROGEN.
Important Notes for Installation:
• Cables must pass through 1/2” NPT Atex cable gland or Atex/IECEx conduit (not included with instrument).
• After connection, make sure to tighten the cable gland and the housing cover to continue to ensure IP66 sealing (IP 65 if with vent valve).
• Open the case only after having disconnected the power supply to the instrument.
• Warning: Check local regulations and warnings on the instrument and in the operating manual for correct use in classified areas.
* Operating ambient temperature is however also determined by the limits of the options and/or the measuring element.