AT2-MS2 – ATEX/IECEx Exd Magnesense2 low differential pressure transmit

Quick Overview

ATEX_WEB_COMHAS     logo_iecex     logo_comhas

• Ranges from 0-0.1 inch W.C. (0-25 Pa) to 28 inch W.C. (6.975 KPa)
• Zero center ranges
• Monitors pressure, air velocity & air flow
• Display LCD optional
• BACnet/Modbus communications

Atex:
CE 1370
II 2G Ex d IIC T6 Gb
Ex II 2D Ex tb IIIC T85°C Db, -60°C≤T amb≤+60°C
Certificate: BVI 14 ATEX 0072

IECEx:
Ex d IIC T6 Gb
Ex tb IIIC T85°C Db
Certificate: IECEx EPS 14.0082

Esecuzione:
IP66 (IP65 with option OPV

SPECIFICATION MAGNESENSE 2

  1. Service: Air and compatible clean and dry gases
  2. Temperature limits: Transmitter: 0 to 150°F (-18 to 66)
  3. Case: -60 to 60°C
  4. Pressure limits: 1 psi max operative pressure 10 psi burst.
  5. Accuracy: ±1%f.s. for ranges:
    0.15” w.c (40 Pa), 0.25” w.c (50 Pa), 0.5” w.c. (100 Pa), 2” w.c. (500 Pa), 3” w.c. (750 Pa), 5” (1250 Pa),
    10” w.c. (2 kPa), 15” w.c. (3 kPa), 25” w.c. (5 kPa), 28” w.c. (6.975 kPa)
    ±2% f.s. for ranges:
    0,1” w.c. (25 Pa), 1” w.c. (250 Pa) and all bi directional ranges
  6. Stability: ±1% f.s. year
  7. Power requirements: 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire)
  8. Output signals: 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire)
  9. Response time: field adjustable 0.5 to 15 sec. time constant, provides a 95% response time of 1.5 to 45 sec. (additional delay in response time due to flame arrestors; from full scale to ø up to 90 sec. depending on model range).
  10. Zero & span adjustments: digital push button (to be made in safe area)
  11. Loop resistance: current output: 0-1250 Ohm max.
  12. Voltage Output: min. load resistance 1 kOhm
  13. Current consumption: 40 mA max
  14. Display (optional): 5 digit LCD
  15. Electrical connections: 3 wire removable European style terminal block for 16 to 22 AWG
  16. Mounting orientation: Diaphragm in vertical position
  17. Supported baud rates: 9600, 19200, 38400, 57600, 76800, 115200
  18. Data size: 8
  19. Parity: none
  20. Stop bits: 1

HOUSING

Housing material: Alluminium (stainless steel optional)
Finishing: Texture epoxy coat RAL7038 suitable for installation in harsh environments.
Process connections: 1/8” female NPT brass (stainless steel optional) in presence of acetylene it is necessary to use stainless steel
Electrical connection: 2 x ½” NPT F standard (cable gland non included)
Dimensions: see drawing below
Weight: 5 Kg ab.

* Operating ambient temperature is defined also according to the options and pressure instrument choosed.

CAUTION FOR USE ONLY WITH AIR OR COMPATIBLE GASES!